Low Voltage Panel

  • Optional insulated busbar system – protection against accidental contact by people or foreign objects and inhibits the spread of any arcing fault
  • Enclosure built in high quality metal sheet.
  • Fully tin plated copper busbars
  • High quality powder coated finish
  • Easy operation and maintenance

Low Voltage Panel Technical Data

– Low voltage panel comprises incoming Air Circuit Breakers, horizontal and vertical busbars and outgoing Air Circuit Breakers / Molded Case Circuit Breakers. Our LV Panels are designed, manufactured and tested for short circuit current up to 85 kA.

TypeRFPB - P
Rated Insulation Voltage (Ui)690 V
Rated Voltage (Un)Up to 440 V 60Hz
Rated Current (In)Up to 3200 A
Rated Short time withstand current (Icw)85 kA for 1 sec
Degree of Protection (IP)IP 54 (as required)
Form of SeparationUp to Form 4B
ApplicationIndoor / Outdoor
Paint Color / ShadeRAL 7032 Powder Coating or (As required)
Bus Duct /Cable EntryBottom / Top Entry (as required)
Applicable StandardIEC 61439-2
Motor Control Center